Graphical Symbols and Abbreviations Standard BS 1635:1990
Introduction
The current standard is BS 1635 : 1990 .
The standard applies simple icons that representing one piece of fire engineering and are called element. You then combine a number of these elements into a symbol, for example the element for any type of extinguisher is a triangle, insert into the triangle the element for water, a circle with a vertical line and you have a Water Extinguisher. You can make them more complex and they are then called applications. The symbol for a hose reel is a semicircle, with the water element inserted, add an outlet which is an arrow, and the element for length of hose in meters and you have an application.
The application for a hose reel shows the length of the hose in metres in the upper right hand corner and although contrary to the standard I believe it should be also apply to portable extinguishers.
The above is only a very brief introduction and the symbols are simple sketches produced by me consequently you need to research the British Standard by purchasing a copy or use the local reference library who may have copies.
Group 1 – Information
Table 1.1 – Convention for indicating zones
Conventions | ||
1.101 | Behind cutting plane – Hidden | |
1.102 | Behind cutting plane – Visible | |
1.103 | Beyond cutting plane – Visible | |
1.104 | Beyond cutting plane – Hidden |
Group 2 – Fire Extinguishers
Table 2.1 – Portable and transportable
Elements | |||
Water2.1E1 | Halon Gas2.1E7 | ||
Foam2.1E2 | Carbon Dioxide Gas2.1E8 | ||
Powder Any Type2.1E3 | Wall Mounted2.1E9 | ||
BC Powder2.1E4 | Transportable,Wheel or Skid Mounted2.1E10 | ||
ABC Powder2.1E5 | Fire Blanket2.1E11 | ||
Gas Any Type2.1E6 |
Symbols |
|||
Any Type2.101 | Any type Gas Extinguisher2.101 + 2.1E6 | ||
Portable Free standing Water Extinguisher2.101 + 2.1E1 | Halon Gas Extinguisher2.101 + 2.1E7 | ||
Portable Free standing Foam Extinguisher2.101 + 2.1E2 | Carbon DiOxide Extinguisher2.101 + 2.1E8 | ||
Dry Powder Extinguisher2.101 + 2.1E3 |
Water Bucket2.110 |
||
BC Dry Powder Extinguisher2.101 + 2.1E4 |
Sand Bucket2.111 |
||
ABC Dry Powder Extinguisher2.101 + 2.1E5 |
Fire Blanket2.101 + 2.1E11 |
||
Applications |
|||
Portable free standing Water Extinguisher2.101 + 2.1E1 + 3.1E6 | Transportable Halon Gas Extinguisher2.101 + 2.1E7 + 2.1E10 + 3.1E6 | ||
Portable wall mounted BC Powder Extinguisher2.101 + 2.1E4 + 2.1E9 + 3.1E6 |
Group 2 – Fire Extinguishers
Table 2.2 – Fixed Installations
Elements | |||
Outlet 2.2E1 | Hydraulic Operation2.2E6 | ||
Inlet 2.2E2 | Manual Operation2.2E7 | ||
Total Application2.2E3 | Mechanical Operation2.2E8 | ||
Actuator Any Type2.2E4 | Pneumatic Operation2.2E9 | ||
Electrical Operation2.2E5 | Thermal Operation2.2E10 |
Symbols | |||
Fixed System Any Type2.201 | Hydraulic Actuator2.2E4 + 2.2E6 | ||
Fixed System Water2.2E3 + 2.1E1 | Manual Actuator2.2E4 + 2.2E7 | ||
Fixed System Foam2.2E3 + 2.1E2 | Mechanical Actuator2.2E4 + 2.2E8 | ||
Fixed System Powder2.2E3 + 2.1E3 | Pneumatic Actuator2.2E4 + 2.2E9 | ||
Fixed System Gas2.2E3 + 2.1E6 | Thermal Actuator2.2E4 + 2.2E10 | ||
Electrical Actuator2.2E4 + 2.2E5 | |||
Applications | |||
Fixed System any Type Local Application2.201 + 2.2E1 | Fixed System Manually Actuated2.201 + 2.2E7 | ||
Drencher System Any Type2.201 + 2.2E1 |
Group 3 – Fire Fighting
Table 3.1 – Fire Fighting Equipment
Elements | |||
Pipe Below Ground3.1E1 (See 1.104) | Indicator or Meter3.1E5 | ||
Pipe Above Ground3.1E2 | Length of hose in metres3.1E6 | ||
Chamber in Ground3.1E3 | Non Return Check Valve3.1E7 | ||
Valve3.1E4 |
Symbols |
|||
|
Fire Main or Riser Any Type3.101 | Ground Hydrant in Chamber Double3.1E3 + 3.1E1 + 3.1E4 + 2.2E1 | |
|
Fire Main Dry3.102 | Pillar Hydrant Single3.1E1 + 3.12 + 3.1E4 + 2.2E | |
|
Fire Main Wet3.101 + 2.1E1 | Pillar Hydrant Double3.1E1 + 3.12 + 3.1E4 + 2.2E | |
|
Fire Main Foam3.101 + 2.1W2 | Fire Point3.109 | |
|
Ground Hydrant in Chamber Single3.1E3 + 3.1E1 + 3.1E4 + 2.2E1 | Hosereel3.110 | |
Applications | |||
|
Dry Fire Main Landing Valve3.101 + 3.1E4 + 2.2E1 | Underground Fire Main3.1E12.1E2 | |
Foam Inlet3.102 + 2.2E2 | Hosereel 45m long3.110 + 3.1E6 + 2.1E1 + 2.2E1 | ||
Underground Fire Main3.1E1 + 2.1E1 | Under ground Fire Main with Metered by Pass3.1E1 + 3.1E3 + 3.1E4 + 3.1E5 |
Group 4 – Fire Alarm
Table 4.1 – Control and Indicating Equipment
Elements |
|||
Sounder4.1E1 | Illuminated Signal4.1E2 | ||
Symbols
|
|||
Control Panel Any Type4.101 | Control Panel Illuminated Signals4.101 + 4.1E2 | ||
Control Panel Sounders4.101 + 4.1E1 | Control Panel Sounders and Illuminated Signals4.101 + 4.1E1 + 4.1E2 | ||
Group 4 – Fire Alarm
Table 4.2 – Initiating Equipment
Elements | |||
Smoke4.2E1 | Beam4.2E3 | ||
Flame4.2E2 |
Symbols |
|||
Detector Any Type4.201 | Gas Detector4.201 + 2.1E6 | ||
Heat Detector4.201 + 2.2E10 | Fire Alarm Manual Call Point4.201 + 2.2E7 | ||
Smoke Detector4.201 + 4.2E1 | Beam Detector4.201 + 4.2E3 | ||
Flame Detector4.201 + 4.2E2 |
Group 4 – Fire Alarm
Table 4.3 – Warning Equipment
Elements | |||
Manual Sounder4.3E1 | LoudSpeaker4.3E3 | ||
Electric Bell4.3E2 | Telephone4.3E4 |
Symbols | |||
Warning Device Any Type4.301 | Warning Device Loudspeaker4.301 + 4.3E3 | ||
Warning Device Manual Sounder4.301 + 4.3E1 | Warning Device Telephone4.301 + 4.3E4 | ||
Warning Device Sounder4.301 + 4.1E1 | Warning Device Visual4.301 + 4.1E2 | ||
Warning Device Bell4.301 + 4.3E2 | |||
Applications | |||
Telephone with Flashing Light4.301 + 4.3E4 + 4.1E2 |
Group 5 – Means of Escape
Table 5.1 – Routes
Elements
|
|||
Directional Arrow5.1E1 | |||
Symbols |
|||
|
Escape Route5.101 | Escape Route, Final Exit5.103 | |
|
Escape Route, Direction to Follow5.102 |
Group 6 – Risk Areas
Table 6.1 – Fire and Explosion
Elements |
|||
|
Flammable Materials6.1E1 | Explosive Materials6.1E3 | |
|
Oxidizing Materials6.1E2 |
Symbols |
|||
|
General Hazard Warning6.101 | Oxidizing Materials Risk Area6.103 | |
|
Flammable Materials Risk Area6.102 | Explosive Materials Risk Area6.104 |
Group 7 – Fire Precautions
Table 7.1 – Building Elements
Elements |
|||
|
Ramp Gradient7.1E1 | Self Closing Automatic Release7.1E8 | |
|
Fire Resistance in Minutes7.1E2 | Vision Panel7.1E9 | |
|
Fire Resisting Glazed Element7.1E3 | Guarding Handrail7.1E10 | |
|
Security Lock7.1E4 | Push Bar Door Ironmongery7.1E11 | |
|
Key in Box7.1E5 | Fusible Link7.1E12 | |
|
Free From Fastenings7.1E6 | Fire Resisting7.1E13 | |
|
Self Closing7.1E7 | Smoke Resisting7.1E14 |
Symbols |
|||
|
Wall Opening with Window7.101 | Door set, Sliding Leaf7.111 | |
|
Wall Opening with Roller Shutter7.102 | Door set, Revolving Leaves7.112 | |
|
Wall Opening with Up and Over Door7.103 | Door set, Sliding/folding, End Hung7.113 | |
|
Door Set, Hinged Leaf7.104 | Door set, Sliding/folding, Centre Hung7.114 | |
|
Door set, Hinged leaf (alternative)7.105 | Stairway, Arrow Indicates Up Direction7.115 | |
|
Door set, Hinged Leaf, Normally Closed7.106 | Ramp, Arrow Indicates Up Direction7.116 | |
|
Door set, Hinged Leaf, Normally Open7.107 | Fire Damper7.117 | |
|
Door set, Hinged Leaf, O[opening Either Way7.108 | Fire Resisting Construction 30 min7.118 | |
|
Door set, Hinged Leaf, Opening 1807.109 | Fire Resisting Construction 30 min’s (for small scale drawings)7.119 | |
|
Door set, Two Hinged Leaves7.110 | ||
Applications |
|||
|
Fire Resisting Glazed Screen7.1E2 + &.7.1E3 7.101 + 7.118 | Final Exit Door set Double Leaves Single Swing with push bar door ironmongery7.110 + 7.1E11 | |
|
Fire Damper in Ductwork7.117 | Ramp Showing Direction of Rise and Gradient7.116 + 7.1E1 | |
|
30 min Fire Resisting Door set, Single Leaf, Single Swing7.118 + 7.104 +7.1E2 + 7.113 | Guarding Rail along side of open Stairwell7.115 + 7.1E10 | |
|
60 min Fire Resisting Door set, Single Leaf, Single Swing7.118 + 7.104 +7.1E2 + 7.1E13 + 7.1E14 | Wall Opening with Roller Shutter 30 min’s Fire Resistance operated by Fusible Link7.102 + 7.1E13 + 7.1E12 | |
|
30 min Fire and Smoke Resisting Door set, Double Leaf, Single Swing, Self Closing. Normally held open on electro magnetic devices7.118 + 7.110 + 7.1E2 + 7.1E8 + 7.1E13 + 7.1E14 |
Group 8 – Emergency Lighting
Table 8.1 – Lighting
Elements |
|||
|
Luminaire Any Type8.1E1 | Luminaire Linear Any Type Enclosed8.1E4 | |
|
Luminaire Any Type, Enclosed8.1E2 | Emergency / Safety8.1E5 | |
|
Luminaire Linear Any Type8.1E3 |
Symbols |
|||
|
Emergency, Enclosed8.101 | Emergency, Linear Self Contained8.104 | |
|
Emergency, Self Contained8.102 | Emergency, Linear Enclosed8.105 | |
|
Emergency, Linear Any Type8.103 | Exit Sign Internally Illuminated8.106 |
Group 9 – Fire Safety Signs
Table 9.1 – Descriptions
Elements |
|||
|
General Prohibition9.1E1 | General Condition Sign9.1E21 | |
|
Smoking is Prohibited9.1E2 | Fire Exit9.1E22 | |
|
Smoking and Flames Prohibited9.1E3 | Slide to Open9.1E23 | |
|
Water as Extinguishing Agent Prohibited9.1E4 | Break to Obtain Access9.1E24 | |
|
General Warning9.1E5 | Push Bar to Open9.1E25 | |
|
Flammable Materials9.1E6 | Directional Arrow (Green)9.1E26 | |
|
Oxidizing Materials9.1E7 | Collection of Firefighting Equipment9.1E27 | |
|
Risk of Explosion9.1E8 | Fire Alarm Call Point9.1E28 | |
|
No Means of Escape9.1E9 | Fire Telephone9.1E29 | |
|
In the Event of a Fire, Avoid use of Lift9.1E10 | Fire Hose Reel9.1E30 | |
|
General Mandatory Sign9.1E11 | Fire Extinguisher9.1E31 | |
|
Fire Action Sign9.1E12 | Foam Inlet9.1E32 | |
|
Fire Door Keep Shut9.1E13 | Dry Riser9.1E33 | |
|
Fire Door Keep Locked9.1E14 | Wet Riser9.1E34 | |
|
Automatic Fire Door Keep Clear9.1E15 | Fireman`s Switch9.1E35 | |
|
Automatic Fire Door, Keep Clear, Close at Night9.1E16 | Open Valve, in the event of a Fire9.1E36 | |
|
Door to be Secured Open9.1E17 | Open Valve before running out Hose9.1E37 | |
|
Door to be Unlocked9.1E18 | Fire Plan9.1E38 | |
|
Gangway Keep Clear9.1E19 | Directional Arrow (Red)9.1E39 | |
|
Fire Escape Keep Clear9.1E20 |
Symbols |
|||
|
Fire Exit9.101 | ||
Applications |
|||
|
Fire Door to be kept shut 7.118 + 7.104 + 9.114 | Fire Exit Door with Sign 7.118 + 7.110 + 8.106 + 9.1E22 |
Group 10 – Smoke Control
Table 10.1 – Venting and Pressurization
Elements |
|||
|
Smoke Vent on Plan10.1E1 | Smoke Vent in Horizontal or Vertical Section10.1E5 | |
|
Smoke Vent over on Plan10.1E2 | Fan10.1E6 | |
|
Roof Light Vent on Plan10.1E3 | Flow Direction Extract10.1E7 | |
|
Roof Light Vent over on Plan10.1E4 | Flow Direction Supply10.1E8 |
Symbols |
|||
|
Space Requiring Smoke Ventilation10.101 | Replacement Air Intake10.111 | |
|
Pressurized Space10.102 | Window Smoke Release Manual10.112 | |
|
Pressurized Space, Single stage10.103 | Window Smoke Release Automatic10.113 | |
|
Pressurized Space, Double Stage10.104 | Pressure Air Supply Point10.114 | |
|
Smoke Reservoir10.105 | Pressurizing Air Intake 10.115 | |
|
Pressure Differential Point10.106 | Smoke Curtain Fixed10.116 | |
|
Smoke Vent Manually Actuated10.107 | Smoke Curtain Automatically Actuated10.117 | |
|
Smoke Vent Automatically Actuated10.108 | Smoke Extraction Fan10.118 | |
|
Smoke Extract Point10.109 | Pressurizing Air Supply Fan10.119 | |
|
Smoke Discharge Point10.110 |
British Standards are available from : – British Standards Online
Categories:Miscellaneous Fire Safety Issues